PREVENT [d]s – carbon monoxide and methane gas safety system

General Details

Detector

Certified quality – the detector holds a Kitemark Certificate issued by British Standards Institution according to the BS EN 50194-1:2009 and BS EN 50291-1:2010 standards

Simple design – friendly shape, easy to integrate in any home design

Dual detection: methane and carbon monoxide – electrochemical sensor and semiconductor sensor inside, designed to sense low levels of carbon monoxide and/or methane gas.

Dedicated – provides an alarm signal well before the carbon monoxide concentration in the house could reach levels dangerous to your health

Double alarm – provides both a visual alarm (red light) and an audible alarm (buzzer)

Remote control – the detector supplies an output signal to activate an ancilliary device which could be a fan, a siren or a shut-off solenoid valve

Knows the difference – designed to avoid false alarms caused by contaminant factors in your home

Auto diagnostic – contains an auto-diagnostic system that constantly checks the detector’s operation. The yellow light continuously turned on indicates a possible malfunction of the detector

Test – features a button for testing in normal working conditions, allowing the user to periodically check the functioning of the detector

Solenoid Valve

Normally open or normally closed safety solenoid valves with manual reset. The closing/opening function is
electrically activated.
This type of device connected to one or more methane gas detectors and/or carbon monoxide
detectors, is suitable for performing locking operations on the gas line.

An incorporated ne mesh lter protects the valve seat and disc as well as downstream components
and prevents dirty contamination (except brass models). All components are designed to withstand
any mechanical, chemical and thermal condition occuring during typical service. Eective
impregnation and surface treatments have been used to improve mechanical sturdiness, sealing and
resistance to corrosion of the components.
Valves are 100% tested by computerized testing machineries and are fully warranted.

Technical Info

Detector

Sensors: Semiconductor SnO2 (CH4) and Electrochemical (CO)
Power supply: 230 V AC(-15% , +10%) 50/60 Hz
Power absorbed: 3.2 VA
Detected gas: Methane and Carbon Monoxide
Sensitivity (CH4): 3% ÷ 20% LEL
Alarm set point (CH4): 8% LEL
Alarm levels (CO):
50 ppm: Between 60 min – 90 min
100 ppm: Between 10 min – 40 min
300 ppm: Between 0 min – 3 min
Initial delay time (CH4): 3 min 10 sec
simultaneously – (CO): 2 min 20 sec
Indicators:
     Visual: Operation: Green LED
                  Alarm: Bicolor LED in Red light
                  Fail: Bicolor LED in Yellow light
     Acoustic: Alarm / Fail: Buzzer minimum 85 dB at 1 m
Sensors lifetime: 5 Years
Contact ratings: 8(2) A @ 250 V AC SPDT3 A @ 250 V AC SPST (optional)
Operating temperature: -10°C ÷ +40°C
Storage temperature: -20°C ÷ +50°C
Humidity limits (non condensing): 20% ÷ 90% rh
Protection grade: IP 42
Case material: ABS V0
Color: White
Size: 115 mm x 75 mm x 43 mm (W x H x D)
Weight: 300 g

 

Solenoid Valve

Connections :
Gas threaded ISO 7/1 from Rp3/8 to Rp2 ½
Flanged PN16 – ISO 7005 from DN40 to DN300
Voltage rating: 230 VAC 50/60 Hz
110 VAC 50/60 Hz
24 VAC; 24 VDC
12 VDC
Voltage tolerance: -15% / +10%
Working temperature: -15°C/+60°C
Max. operating pressure: 600 mbar (60 kPa)
6 bar (600 kPa)
Closing time: < 1 sec.
Filter (except brass models): 600 μm, metal mesh
Protection grade: IP 54 (EN 60529)
Cable gland: PG 9
Coil winding insulation: Clasa H (200°C)
Coil thermal resistance: Clasa F (155°C)
Materials in contact with gas: Aluminum alloy, Brass,
Stainless steel, Plated steel, Anaerobic adhesive,
Nitrile rubber (NRB), Polytetrauoroethylene (PTFE)